Step 0: Work out what has failed
Walk through the RV and note what works. The pattern tells you where to look.
| What you see | Likely cause | What to check | Fix or next step |
|---|---|---|---|
| 12 V lights work, 120 V outlets and air conditioner dead | No shore power, tripped pedestal or RV breaker, GFCI, surge protector fault | Pedestal breaker, protector display, RV main breaker and GFCI | Reset once; if it trips again, stop |
| 120 V works, 12 V lights and pump dead | Battery disconnect off, blown DC fuse, failed converter or loose battery connection | Disconnect switch, fuse panel, battery voltage, converter output | Follow Steps 6 to 9 below |
| Everything dead | Two problems, a dead battery plus no shore power, or a main disconnect | Both systems, starting with 120 V | Restore shore power first, then check the 12 V side |
| Only some outlets dead | Tripped GFCI upstream, a tripped branch breaker, or a loose connection | GFCI test/reset buttons (kitchen, bath, exterior); branch breakers | Reset a GFCI; a loose or hot outlet needs a technician |
| Power works for a while then cuts out | Overload, low voltage, overheating plug or cord, protector tripping | What starts it; plug warmth; voltage reading | Reduce loads; replace damaged cords; see Step 4 |
| Lights dim when appliances start | Low pedestal voltage or weak battery | Voltage display; battery voltage | Move pedestals, reduce loads, charge battery |
| Everything dead after cold weather | Flat or frozen lead-acid battery, lithium battery low-temperature cut-off | Battery voltage, case condition, battery management display | Warm and charge safely or replace; see winter section |
Step-by-step diagnosis, safest and cheapest first
Step 1: Look and smell before you touch
Check for burning odours, warm or discoloured plugs, scorched outlets, water on the floor near panels, and a surge protector showing a fault light. If anything looks scorched or smells hot, disconnect from shore power and stop. That is a professional job.
Step 2: Check the campground supply
- Look at the pedestal breaker (it should be on and not in the middle position) and any GFCI receptacle on the pedestal. Press the reset button if it has tripped.
- Ask the campground whether there is an outage or maintenance, or whether the pedestal is overloaded at busy times.
- Confirm you are using the correct receptacle: 30 A (TT-30), 50 A (14-50) or a 15 A or 20 A household outlet with an adapter. An RV drawing 30 A may trip a 15 A circuit very quickly. If you can, plug a known-good device such as a lamp, or a plug-in receptacle tester, into the pedestal first.
- Do not open pedestal panels or probe pedestal terminals. If another outlet is dead, tell the campground rather than trying to fix it.
Step 3: Check your power cord and adapters
- Fully seat the plug. A partially seated plug can cause heat and dropouts.
- Feel the plug and any adapter after the load has been running. Warm is normal, hot or discoloured is not. Melted or pitted blades mean stop using it and replace the cord end.
- Use a correctly rated cord (30 A or 50 A) and keep extensions as short as possible. A thin household extension cord can overheat or drop voltage.
Step 4: Read the surge protector or EMS
A surge protector or electrical management system (EMS) sits between the pedestal and the RV and shows faults such as low voltage, high voltage, open ground, reverse polarity, or a delay while it tests the supply. Many such devices wait a minute or two after connecting before they switch power on. Typical protective cut-offs are around 104 V low and 132 V high on a 120 V line, but check the figures for your unit. If it reports reverse polarity, open ground or open neutral, do not bypass it: move to another site or ask the campground to correct it. See Surge protector vs EMS and 30 A vs 50 A service.
Low voltage is common in summer when many air conditioners run on the same campground feeder. Persistent readings below about 105 V can damage motors and compressors, so turn off the air conditioner and heavy loads and wait for the voltage to recover.
Step 5: Check the breakers and GFCIs inside the RV
- Open the hinged door of the RV's breaker panel (the one that exposes the breaker handles, not the inner cover) and check the main breaker and branch breakers. A tripped breaker sits between on and off. Switch it fully off, then on.
- Reset a breaker only once. If it trips again straight away, there is a fault or an overload, so stop.
- Find every GFCI outlet (usually kitchen, bathroom and exterior). Press TEST then RESET. In many RVs, one GFCI protects several outlets downstream, so a dead outlet may be fixed by a reset somewhere else.
- Check total load. An RV air conditioner commonly draws in the neighbourhood of 12 to 16 A running, a microwave about 10 to 13 A, and an electric water heater element roughly 12 A. A 30 A service cannot run all three together, and a 15 A household circuit cannot run even two. Turn heavy loads off, reset, and add them back one at a time.
- On generator power, check the generator's own breaker, fuel and the transfer switch (automatic or manual) as well. See Generator problems and Generator operation safety.
Step 6: Check the 12 V battery and disconnect switch
- Turn the battery disconnect or master switch to ON. Many RVs also have a separate chassis battery switch.
- Measure battery voltage with a multimeter on DC volts, with loads off. A fully charged 12 V lead-acid or AGM battery reads about 12.6 to 12.8 V. Around 12.0 V is roughly half charged. Under about 11.8 V is nearly flat. Lithium (LiFePO4) batteries have a flat voltage curve, so read the battery monitor or app instead. A lithium battery that has shut itself off will read near zero at the terminals until it is reset or recharged. Follow the manufacturer's instructions.
- Check the terminals for corrosion, and tighten loose clamps. Keep tools away from the positive terminal and the frame.
- If the battery is flat, plug in or run the generator or tow vehicle so the converter or charger can recharge it. A battery that will not hold a charge needs testing. See Battery not charging and Battery maintenance.
Step 7: Check the 12 V fuses
The 12 V fuse panel is usually near the converter or distribution panel. Blade fuses are colour-coded by rating: for example, 5 A tan, 7.5 A brown, 10 A red, 15 A blue, 20 A yellow, 25 A clear or natural and 30 A green. Look for a broken element or darkened glass. A more reliable check, with the battery connected and the circuit switched on, is to measure DC voltage from each side of the fuse to ground: if you see 12 V on one side and none on the other, the fuse is blown. Replace with the same rating only. If the new one blows, there is a short or an overload. Do not keep trying.
Step 8: Check the converter or charger
When the RV is on shore power, the converter turns 120 V into 12 V DC, running the 12 V loads and charging the house battery. If 120 V works but the 12 V side is dead or the battery never charges, suspect the converter's DC fuse or breaker, a loose connection, or a failed converter. Measure the voltage at the battery while on shore power. A healthy converter or charger usually holds the battery at roughly 13.2 to 14.6 V depending on the charge stage, but the figures vary by model and battery type, so check yours. If the battery sits at its resting voltage with shore power connected, the charger is probably not charging. Internal converter faults are a technician job. See Converter and battery charging.
Step 9: Know when to stop
If you reach this step without finding a cause, stop. Further diagnosis means working inside energized panels, testing wiring, or replacing a converter, inverter or transfer switch. Those are professional tasks. Write down what works, what doesn't, and any fault lights or voltages you saw.
Canadian winter and travel specifics
- Cold batteries: Lead-acid batteries lose a noticeable share of their capacity in the cold, and a deeply discharged one can freeze at only a few degrees below zero. Do not charge a battery with a bulging or cracked case. Many lithium batteries will not accept charge below 0 °C unless they have heating or low-temperature protection. See Lithium battery winter charging.
- Shore power in freezing weather: Frost and moisture can trip pedestal GFCIs. Keep connections off the snow, use a weather cover where available, and never use a damaged cord to "dry out" a connection.
- Heating loads: A 1,500 W electric heater draws about 12.5 A at 120 V. On a 15 A circuit, that leaves almost nothing else. On a 30 A service, it competes with the water heater and microwave.
- Dry camping: In winter, short days and a low sun reduce solar charging, and furnaces draw more at night. Watch battery voltage and run the engine or generator in an open, well-ventilated area, away from windows and vents.
- Service: Canadian shore power is 120 V, 60 Hz. Many campgrounds in the north and in remote parks have limited amperage, so ask what the site provides.
What not to do
- Do not bypass or defeat a surge protector, GFCI or breaker.
- Do not use a "cheater" adapter that removes the ground pin.
- Do not use a larger fuse or a wire to jump a fuse.
- Do not probe live pedestal terminals or work inside an energized panel.
- Do not charge a frozen or swollen battery.
- Do not run a generator inside a garage or near open windows.
When to call a professional
Call a qualified RV electrician or mobile RV technician if breakers trip repeatedly, a plug or outlet is scorched, only some outlets are dead after resetting the GFCIs, you feel a tingle from metal surfaces, the converter or transfer switch appears faulty, or the problem is intermittent. Electrical work in Canada must meet applicable codes and local rules, so ask about qualifications. Browse the RV repair directory for a technician in your province, and give them the symptom pattern from Step 0, any fault light and any voltage readings.
Quick checklist
- Scope identified: 12 V, 120 V or both
- No burning smell, melted plug or water near electrical equipment
- Pedestal breaker and GFCI checked; campground asked about outages
- Cord fully seated, correctly rated and not hot
- Surge protector or EMS display read; voltage in range
- RV main and branch breakers reset once; all GFCIs tested and reset
- Heavy loads reduced and added back one at a time
- Battery disconnect on; battery voltage checked and terminals clean
- 12 V fuses checked and replaced with the same rating only
- Converter or charger output checked, or a technician called
Common questions
Why do my lights work but my outlets don't?
Lights usually run on the 12 V battery system and outlets on 120 V. Outlets dead means no shore power, a tripped breaker or GFCI, or a surge protector fault. Check Steps 2 to 5.
Why do my outlets work but my lights don't?
The 12 V side has a problem: a battery disconnect that is off, a blown fuse or a dead converter and battery. See Steps 6 to 8.
Why does the breaker keep tripping when I run the air conditioner?
You may be overloading the circuit, the pedestal may be weak or the voltage low. Turn off other large loads and try again. If it trips with nothing else on, the air conditioner or its wiring may be faulty, so have it checked.
Can I plug a 30 A RV into a household outlet?
With the right adapter, yes. A 15 A outlet limits you to roughly 1,800 W, so you may run only a few small loads, and a long or thin extension cord can cause voltage drop. Don't run the air conditioner and other large appliances together.
My surge protector shows reverse polarity. What now?
That means the pedestal is wired wrongly. Do not bypass the protector. Move to another site or ask the campground to correct it.
How can I tell if my battery is dead or just disconnected?
Check the disconnect switch and terminals first, then measure voltage. A reading near 12.6 V or higher means it is charged. A reading below 12 V means it needs charging, and a reading near zero may mean a broken connection or a protective shut-off.
Related guides
- RV electrical troubleshooting repair guide
- 12 V and 120 V electrical systems explained
- Connecting RV shore power
- 30 A vs 50 A service
- Surge protector vs EMS
- Converter and battery charging
- 12 V lights flicker or dim
- Symptom finder
🔧 Still no power? Find a technician
If the checks above do not fix it, look for an RV electrical technician: a mobile RV technician or a dealer service department that works on converters, chargers, inverters, batteries and shore-power wiring.
Bring in a professional when
- The pedestal and breakers check out but the RV still has no 120 V
- You find burnt smell, scorched plugs or hot cords
- The surge protector or transfer switch shows a fault
- Some outlets work and others do not
When you call, say
Mention what works and what does not, and any surge protector error code.
Worth asking
Ask whether they can test the converter or charger, battery bank and shore-power inlet, and what a diagnostic visit costs.